- Functions: Voltage, current, power, power factor, frequency; Energy forward/reverse; Peak Demand; THD; Voltage and current harmonics (to 50th); Flicker; Unbalance
- Rapid voltage change events; Interharmonics (to 50th); Dips, swells, interruption and transient events tables; Mains signaling; Inrush current
- Recording: Trend
Accuracy | |
Voltage | Range: 1000 V Maximum resolution: 0.1 V Intrinsic accuracy at reference conditions (% of reading +% of range): ±0.1 % of nominal voltage |
i17xx-flex 3000IP 24 3000 A | Range: 300, 3000 A Maximum resolution: 0.01 A (min. 3.0 A)3, 0.1 A Intrinsic accuracy at reference conditions (% of reading +% of range): ±(1% + 0.03%) |
Voltage | Range: 42.5 to 69 Hz Maximum resolution: 0.01 Hz Intrinsic accuracy at reference conditions (% of reading +% of range): ±(0.1%)2 |
Auxiliary Input | Range: ±10 V DC Maximum resolution: 0.1 mV Intrinsic accuracy at reference conditions (% of reading +% of range): ±(0.2% + 0.02%) |
Voltage Min/Max | Range: 1000 V Maximum resolution: 0.1 V Intrinsic accuracy at reference conditions (% of reading +% of range): ±0.2 % of nominal input voltage |
Current Min/Max | Range: Defined by accessory Maximum resolution: Defined by accessory Intrinsic accuracy at reference conditions (% of reading +% of range): ±(5% + 0.2%) |
THD on Voltage | Range: 1000% Maximum resolution: 0.10% Intrinsic accuracy at reference conditions (% of reading +% of range): ± 2.5% |
THD on Current | Range: 1000% Maximum resolution: 0.10% Intrinsic accuracy at reference conditions (% of reading +% of range): ± 2.5% |
Voltage Harmonics 2nd to 50th | Range: 1000 V Maximum resolution: 0.1 V Intrinsic accuracy at reference conditions (% of reading +% of range): ≥1 V: ±5% of reading, <1 V: ±0.05 V |
Current Harmonics 2nd to 50th | Range: Defined by accessory Maximum resolution: Defined by accessory Intrinsic accuracy at reference conditions (% of reading +% of range): ≥3% of current range: ±5% of reading, <3% of current range: ±0.15% of range |
Flicker PLT, PST | Range: 0 to 20 Maximum resolution: 0.01 Intrinsic accuracy at reference conditions (% of reading +% of range): 5% |
Electrical Specifications | |
Voltage Range | 100 to 500 V using safety plug input when powering from the measurement circuit 100 to 240 V MA-C8 and using standard power cord (IEC 60320 C7) |
Power Consumption | Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter) |
Efficiency | ≥68.2% (in accordance with energy efficiency regulations) |
Maximum No-Load Consumption | <0.3 W only when powered using IEC 60320 input |
Mains Power Frequency | 50/60 Hz ±15% |
Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
On-Battery Runtime | Typically 4 hours |
Charging Time | <6 hours |
Data Acquisition | |
Resolution | 16-bit synchronous sampling |
Sampling Frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency |
Input Signal Frequency | 50/60 Hz (42.5 to 69 Hz) |
Circuit Types | 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies) |
Data Storage | Internal flash memory (not user replaceable) |
Memory Size | Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events |
Basic Interval | |
Measured Parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
Averaging Interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
Averaging Time Min/Max Values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms) |
Demand Interval (Energy Meter Mode) | |
Measured Parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy |
Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off |
Power Quality Measurements | |
Measured Parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation |
Averaging Interval | 10 min for all parameters 2 hrs (long term Flicker PLT) 150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT) |
Individual Harmonics | 2nd to 50th harmonic Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only |
Interharmonics | 1st to the 50th interharmonic |
Total Harmonic Distortion | Calculated on 50 voltage harmonics |
Events | Voltage: dips, swells, interruptions, current: inrush current |
Triggered Recordings | RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30) Waveform of voltage and current up to 200 ms, 10/12 cycles Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120 s |
Inrush | RMS profile based on ½ cycle RMS steady state triggering |
Flicker | In accordance with IEC 61000-4-15 and IEEE 1453 |
Mains Signaling | Two user defined frequencies up to 3 kHz |
PQ Health | Summarizes power quality measurements in one table. Detailed data available for each parameter |
EN 50160 | Compliance with standard |
Programmable PQ Limits | Enables user defined limits for local standards compliance |
Standards Compliance | |
Harmonics | IEC 61000-4-7: Class 1 IEEE 519 (short time and very short time harmonics) |
Power Quality | IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device) |
Power | IEEE 1459 |
Power Quality Compliance | EN 50160 |
Safety | General: IEC 61010-1: Pollution Degree 2 Measurement: IEC 61010-2-033: CAT IV 600 V/CAT III 1000 V Power Supply: Overvoltage Category IV, Pollution Degree 2 Li-ion Battery: IEC 62133 |
Interfaces | |
USB-A | File transfer via USB flash drive, firmware updates, max. supply current: 120 mA |
Wi-Fi | File transfer and remote control via direct connection or Wi-Fi infrastructure |
Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or Wi-Fi/BLE adapter, check for availability) |
USB-Mini | Data download device to PC |
Voltage Inputs | |
Number of Inputs | 4 (3 phases referenced to neutral) |
Maximum Input Voltage | 1000 Vrms, CF 1.7 |
Input impedance | 10 MΩ |
Bandwidth | 42.5 Hz to 3.5 kHz |
Scaling | 1:1 and variable |
Measurement Category | 1000 V CAT III/600 V CAT IV |
Current Inputs | |
Number of Inputs | 4 (3 phases and neutral), mode selected automatically for attached sensor |
Input Voltage | Clamp input: 500/50 mVrms; CF 2.8 Rogowski coil input: 150/15 mVrms at 50 Hz, 180/18 mVrms at 60 Hz CF 4 all at nominal probe range |
Range | 1 to 150 A/10 to 1500 A with thin flexible current probe i17XX-flex1500 IP 24 |
Bandwidth | 42.5 Hz to 3.5 kHz |
Scaling | 1:1 and variable |
Auxiliary Inputs | |
Number of Inputs | 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously) |
Input Range | 0 to ± 10 V DC, or 0 to ± 1000 V DC (with optional adapter), 1 reading/s |
Scale Factor | Format: mx + b (gain and offset) user configurable |
Displayed Units | User configurable (7 characters, for example, °C, psi, or m/s) |
Wireless Bluetooth Connection | |
Number of Inputs | 2 |
Supported Modules | Fluke Connect® 3000 series |
Acquisition | 1 reading/s |
Environmental Specifications | |
Operating Temperature | -13 to 122°F (-25 to 50°C) |
Storage Temperature | Without battery: -13 to 140°F (-25 to 60°C) With battery: −4 to 122°F (-20 to 50°C) |
Operating Humidity | IEC 60721-3-3: 3K6: -13 to 86°F (-25 to 30°C): ≤100% 104°F (40°C): 55% 122°F (50°C): 35% |
Operating Altitude | 6561.7′ (2000 m) up to 13,123.4′ (4000 m) derate to 1000 V CAT II/600 V CAT III/300 V CAT IV |
Storage Altitude | 39,370.1′ (12,000 m) |
Enclosure | IEC 60529: IP50 IEC 60529: IP65 with IP65 rated voltage connector |
Vibration | IEC 60721-3-3 /3M2 |
Electromagnetic Compatibility (EMC) | EN 61326-1: Industrial CISPR 11: Group 1, Class A IEC 61000-6-5 Power station environment Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 |
General Specifications | |
Dimensions | 9.1 x 7.1 x 2.1″ (23 x 18 x 5.4 cm) |
Weight | 2.2 lbs (1 kg) |
Tamper Protection | Accept securing cables (max. Φ 6mm) |
Troubleshoot, quantify energy usage and perform quality of service surveys easier than ever
It provides you with fast and easy access to the data you need to make real-time decisions, about critical power quality and energy.
Compact and rugged, this three-phase power quality logger is specifically for technicians and engineers who need the flexibility to troubleshoot, quantify energy usage and analyze power distribution systems. Fully compliant with international power quality standards such as IEC 61000-4-30 and capable of simultaneously logging up to 500 parameters while also capturing events, this unit helps uncover intermittent and hard-to-find power quality issues more easily than ever. It comes equipped with an Energy Analyze plus software which quickly assesses the quality of power at the service entrance, substation, or at the load, according to national and international standards like EN 50160 and IEEE 519.
An optimized user interface, flexible current probes, and an intelligent measurement verification function that allows you to digitally verify and correct connections make setup easier than ever and reduce measurement uncertainty. Minimize your time in potentially hazardous environments and reduce the hassle of suiting up in PPE by using a wireless connection (WiFi) to view data directly in the field.
- Measure all three voltage and current phases plus the neutral current
- Comprehensive logging
- Measure with premium accuracy
- Capture dips, swells and interruptions
- Measure key power quality parameters
- Optimized user interface
- Flexible power supply
- Rugged and reliable
- Two external USB ports
- Ethernet connectivity
- Compact size
- Highest safety rating in the industry
- Optimized measurement accessories
- Security
Features
- “In-workshop” or “in-the-field” setup and download through PC application software: simple download using USB memory stick, WiFi download, wired ethernet connection or via USB cable
- Energy Analyze plus application software: download and analyze every measured detail of energy consumption and power quality state-of-health with automated reporting
- One touch reporting: create standardized reports according to commonly used standards like EN 50160, IEEE 519, GOST 33073 or export data in PQDIF or NeQual compatible format for use with third party software
- Advanced analysis: choose any available logged parameter to create a highly customized view of logged measurements for advanced correlation of data
Software Features