Verify the proper operation of automatic circuit reclosers under simulated fault conditions
Efficiently test virtually all single or three phase direct acting reclosers and sectionalizers
Perform primary injection testing of electronically controlled reclosers
Model | RCL-19 | RCL-47 | |
Input | Voltage/Current (one must be specified) |
208-220 V, 100 A 230-240 V, 90 A 416-440 V, 50 A 460-480 V, 45 A |
440 V, 125 A 480 V, 115 A |
Frequency | Single Phase, 60 Hz (Other voltages and frequency are available upon request) |
Single Phase, 60 Hz (Other voltages and frequency are available upon request) |
|
Output | Power | 19 kVA | 47 kVA |
Tap 1 |
0-7.50 VAC, 2500 A |
0-7.50 VAC, 2500 A |
|
2 |
0-15.0 VAC, 1250 A |
0-15.0 VAC, 2500 A |
|
3 |
0-30.0 VAC, 625 A |
0-30.0 VAC, 1560 A |
|
4 |
0-60.0 VAC, 313 A |
0-60.0 VAC, 783 A |
|
5 |
0-150 VAC, 125 A |
0-150 VAC, 313 A |
|
6 |
0-300 VAC, 63 A |
0-300 VAC, 156 A |
|
7 |
0-600 VAC, 32 A |
0-600 VAC, 78 A |
|
Duty Cycle | 30 min ON / 30 min OFF @ 100% of output rating 90 sec ON / 5 min OFF @ 200% of output rating 30 sec ON / 5 min OFF @ 300% of output rating |
30 min ON / 30 min OFF @ 100% of output rating 90 sec ON / 5 min OFF @ 200% of output rating 30 sec ON / 5 min OFF @ 300% of output rating |
|
Instrumentation | Current Measurement | ||
Ranges | 0-30/100/300/3000/7500 A | 0-30/100/300/3000/7500 A | |
Accuracy | ± 0.5% of each range, ± last digit | ± 0.5% of each range, ± last digit | |
Timer | |||
Ranges | 0-9999 sec, 0-9999 cycles | 0-9999 sec, 0-9999 cycles | |
Resolution | 0.001 second; 0.01 cycles | 0.001 second; 0.01 cycles | |
Accuracy | ±1 digit or 0.1% of reading (seconds mode) ±1 digit or 1% of reading (cycles mode) |
±1 digit or 0.1% of reading (seconds mode) ±1 digit or 1% of reading (cycles mode) |
- Circuit breaker protection
- Overload and over temperature protection
- Short circuit protection
- Output current indicator red-green light
- Output will be terminated if the recloser exceeds the allowed time to lock-out
- Emergency Off pushbutton
- Security circuit
- Thermal overload protection
- Desktop Computer and WIN RCL software included Interface port for optional printer Casters with brakes for ease of mobility
- Tow ring and lifting eyes
- Operation/maintenance manual